Power System Operation with Large Scale Stochastic Wind Power Integration by Tao Ding

Power System Operation with Large Scale Stochastic Wind Power Integration by Tao Ding

Author:Tao Ding
Language: eng
Format: epub
Publisher: Springer Singapore, Singapore


Table 3.6 lists the generator reactive power limit and scheduled voltage, the initial interval analysis results for reactive power and voltage magnitude before bus type conversion, and the final interval analysis results after bus type conversion. The ‘Initial solution’ column represents the case without considering reactive power limit, and ‘Final solution’ column shows the case with reactive power limit considered. Table 3.6 also shows reactive power outputs of generator 3, 9 and 12 are out of limit, as highlighted in red and bold font. Therefore, the bus types for those generator buses are changed from PV to PQ and the solution is recalculated.Table 3.6Interval solution of generator reactive power and voltage magnitude with reactive power limit enforced